Key Features

  • Two, four- or six-way units available
  • Apollo, Argus Vega or Hochiki protocols available
  • Integral power supply
  • Robust steel enclosure matches Kentec’s range of Fire control panel styling
  • Space for 7Ah batteries
  • Power Healthy and Power Fault indicators

Description

Product Details

body { font-family: Arial, sans-serif; line-height: 1.6; color: #333; max-width: 900px; margin: 0 auto; padding: 20px; }
h2 { color: #c41e3a; border-bottom: 2px solid #c41e3a; padding-bottom: 10px; }
h3 { color: #444; margin-top: 25px; }
ul { margin: 10px 0; padding-left: 20px; }
li { margin-bottom: 8px; }
table { width: 100%; border-collapse: collapse; margin: 15px 0; }
th, td { border: 1px solid #ddd; padding: 10px; text-align: left; }
th { background-color: #f5f5f5; font-weight: bold; }
tr:nth-child(even) { background-color: #fafafa; }
.highlight { background-color: #fff3cd; padding: 2px 6px; border-radius: 3px; font-weight: bold; }
.note { background-color: #e7f3ff; border-left: 4px solid #2196F3; padding: 12px; margin: 15px 0; }

Kentec 6 Output Addressable Sounder Controller Unit (Apollo Protocol) — A1725603

The Kentec A1725603 is an enclosure containing Apollo XP95 protocol sounder modules giving 6 x monitored sounder outputs. It includes an integral 5.25A PSU with space for up to 2 x 12V 7Ah SLA batteries.

Kentec addressable sounder controller units enable additional, distributed power and control for sounder circuits in situations where there are insufficient circuits at the fire alarm control panel or where additional power is required to power heavily loaded sounder circuits.

Sounder control modules for any of the protocols supported by Kentec analogue addressable control panels are available in a steel enclosure designed to match the appearance of all Kentec’s fire alarm control panel range.

All units contain mains powered battery charger/power supply, they have space for up to 7 Ah batteries.

Indicators are provided for power healthy and power fault conditions and power fault conditions are signalled to the fire alarm control panel as a sounder fault.

Key Features of the A1725603

  • Apollo Protocol
  • Integral 5.25A power supply
  • Robust steel enclosure matches Kentec’s range of fire control panel styling
  • Space for 7Ah batteries
  • Power Healthy and Power Fault indicators

Product Specification

FeatureSpecification
Construction1.2mm mild sheet steel
IP RatingIP30
FinishEpoxy powder coated
Colour — Lid & BoxBS 00 A 05 grey — fine texture
Colour — LabelsRAL 7047 light grey — satin
Weight10kg
Mains Voltage Supply230V AC
Mains Fuse3A, 1¼ inch
Battery Charge Fuse20mm x 5mm, 500 milliamp
Battery Capacity7Ah 12V (2 per panel)
Operating Temperature-5°C to +50°C
Operating HumidityTo 95% (non condensing)
ProtocolApollo XP95
Sounder Outputs6
PSU5.25A
Size (mm)500 x 355 x 108