Notifier FMM-101 Intelligent Mini Monitor Module – Class B Dry-Contact Input

£33.48

Availability: 5 in stock SKU: FMM-101 Categories: , Brand:

The Notifier FMM-101 is a compact addressable monitor module designed for Class B (Style B) dry-contact devices such as heat detectors and pull stations, with direct SLC loop integration and high noise immunity.

Description

The Notifier FMM-101 Intelligent Mini Monitor Module is a compact, addressable device for use with intelligent two-wire fire alarm systems. Designed to monitor a Class B (Style B) circuit of normally open contact devices, the FMM-101 provides seamless integration of conventional input devices into addressable systems.Its small footprint (1.3″ H × 2.75″ W × 0.5″ D) makes it ideal for installation inside single-gang electrical boxes, positioned behind the device it supervises. Addressing is configured via onboard rotary switches, supporting address ranges of 01–159 on FlashScan loops and 01–99 on CLIP protocol loops.With built-in type identification, the FMM-101 is automatically recognised as a monitor module by the fire alarm control panel. It is powered directly from the SLC loop, eliminating the need for auxiliary power, and is built with robust EMF and RFI immunity for reliable performance in electrically noisy environments.

Key Features

  • Class B Circuit Monitoring: Supervises a dry-contact input circuit
  • Compact Miniature Design: Easily mounts in single-gang boxes
  • Addressable via Rotary Switches: Supports FlashScan and CLIP protocols
  • No Additional Power Needed: Powered directly from the SLC loop
  • Built-In Device Identification: Automatically recognised by the control panel
  • High Noise Immunity: Resistant to EMF and RFI interference
  • Tinned, Stripped Leads: Facilitates quick and easy installation

Applications

  • Integrating conventional pull stations into addressable fire systems
  • Monitoring waterflow switches or heat detectors
  • Ideal for retrofits where space-saving is critical

Additional information

Manufacturer

Honeywell International

Brand

Notifier

Model No

FMM-101

Nominal Op+A1:B13erating Voltage: 15-32 VDC
Average Operating Current 375µA maximum (group poll); 350 µA (direct poll); 600 µA Max. (Communicating, IDC Shorted)
EOL resistance: 47K Ohms
Maximum SLC Wiring Resistance 40 Ohms
Maximum IDC Wiring Resistance 1500 Ohms
Maximum IDC Voltage 11 Volts
Maximum IDC Current 450µA
Temperature Range 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 10% to 93% Non-condensing
Wire Length 6˝ minimum